Experimental Investigation of the Effect of Ceramic Bed Configuration on the Thermal Performance of a Regenerative Ventilation System

Authors

  • Krzysztof ŚMIAŁEK Institute of Heat Engineering, Warsaw University of Technology, Warsaw, Poland Author
  • Andrzej GRZEBIELEC Institute of Heat Engineering, Warsaw University of Technology, Warsaw, Poland Author

Keywords:

ceramic heat regenerator, regenerative ventilation, heat recovery, thermal effectiveness, heat transfer coefficient, airflow characteristics, honeycomb structure

Abstract

Ceramic regenerators are increasingly considered for heat recovery in ventilation systems due to their high thermal capacity and large heat-transfer surface area. However, their thermal performance depends on the interaction between regenerator configuration, airflow conditions and the ability of the storage material to accumulate and release heat during cyclic operation. This study aimed to experimentally investigate the effect of ceramic regenerator configuration on airflow characteristics, heat-transfer performance and temperature efficiency. An experimental facility simulating the cyclic operation of a regenerative ventilation system was used to investigate four configurations consisting of one to four ceramic honeycomb blocks connected in series. The fan was operated at the same maximum speed setting for all configurations, while airflow rate, temperature and heat-transfer parameters were measured under cyclic operating conditions. Temperature efficiency was determined directly from the experimental data in accordance with PN-EN 13141-8:2023-02. Reducing the number of ceramic blocks resulted in a substantial increase in mean air velocity, from 4.44 to 12.0 m/s, due to the lower flow resistance of the shorter regenerator bed. The experimentally determined heat-transfer coefficient increased from 28 W/(m²·K) for four blocks to 102 W/(m²·K) for a single block. Despite the highest heat-transfer coefficient, the single-block configuration exhibited the lowest temperature efficiency, reaching 29.74%. Among the investigated configurations, the three-block configuration exhibited the highest temperature efficiency, reaching 85.71%, compared with 82.98% and 74.25% for the four- and two-block configurations, respectively. The results indicate that regenerator performance is governed by a balance between heat-transfer intensity and thermal storage capacity. Under the investigated operating conditions, increasing airflow velocity or reducing regenerator length did not necessarily improve overall thermal performance, highlighting the importance of considering regenerator configuration together with airflow conditions and operating-cycle duration.

Downloads

Published

2026-06-28

Issue

Section

Research articles